How to Install and Remove Control ActiveX
Even though you have already installed an ActiveX control on your computer, you must also make it known to the InTouch HMI by installing it to WindowMaker.
When you remove a control from WindowMaker, it is not deleted from your computer. It is simply removed from memory and does not function.
To install an ActiveX control
On the Special menu, point to Configure and then click Wizard/ActiveX Installation. The Wizard/ActiveX Installation dialog box appears.
Click the ActiveX Control Installation tab. The ActiveX Control Installation property sheet appears.
In the Installed ActiveX controls list, select the control to install in the Available ActiveX controls list and then click Install.
Tip To select multiple controls, use the SHIFT key or CTRL key.
Click OK.
To remove an ActiveX control
On the Special menu, point to Configure and then click Wizard/ActiveX Installation. The Wizard/ActiveX Installation dialog box appears.
Click the ActiveX Control Installation tab. The ActiveX Control Installation property sheet appears.
In the Installed ActiveX controls list, select the control to remove from your application and then click Remove. A message appears asking you to confirm the deletion.
Tip To select multiple controls, use the SHIFT key or CTRL key.
Click Yes to remove the control. The control is moved to the Available ActiveX controls list.
Click OK.
Alarm Viewer Control ActiveX Properties Wonderware Intouch
Alarms and Events Window Popup Wonderware Intouch :-https://youtu.be/fHKgPYI8agA
You can set the value an Alarm Viewer control property directly using a script or you can assign it to an InTouch tag or I/O reference. For more information about setting properties, see Scripting ActiveX Controls.
The following table lists the Alarm Viewer control properties.
AckAllMenu
Discrete
Enables/disables Ack All menu item.
AckAlmColorRange1
Integer
Sets color to be used to show acknowledged alarms with priorities in the range 1 to ColorPriorityRange1. The default priority range is 1 to 250.
AckAlmColorRange2
Integer
Sets color to be used to acknowledged alarms with priorities in the range ColorPriorityRange1 to ColorPriorityRange2. The default priority range is 250 to 500.
AckAlmColorRange3
Integer
Sets color to be used to acknowledged alarms with priorities in the range ColorPriorityRange2 to ColorPriorityRange3. The default priority range is 500 to 750.
AckAlmColorRange4
Integer
Sets color to be used to acknowledged alarms with priorities in ColorPriorityRange3 to 999. The default priority range is 750 to 999.
AckOthersMenu
Discrete
Enables/disables Ack Others menu item.
AckSelectedGroupsMenu
Discrete
Enables/disables Ack Selected Groups menu item.
AckSelectedMenu
Discrete
Enables/disables Ack Selected menu item.
AckSelectedPrioritiesMenu
Discrete
Enables/disables Ack Selected Priorities menu item.
AckSelectedTagsMenu
Discrete
Enables/disables Ack Selected Tags menu item.
AckVisibleMenu
Discrete
Enables/disables Ack Visible menu item.
AlarmQuery
Message
Sets the initial alarm query. This field accepts text only; it does not accept tags. The following example uses the full path to the alarm group:
\NodeInTouch!Group
This example uses the full path to the local alarm group:
InTouch!Group
This example uses another Group List:
GroupList
AlarmState
Message
Default alarm state to query (All, UnAck, Ack).
AlmRtnColor
Integer
Sets the color for alarms that have returned to normal and were unacknowledged. This color is also used for alarms that returned to normal from the acknowledged state but the acknowledgement state transition was not observed.
AutoScroll
Discrete
If the user scrolls the list from the beginning, this automatically jumps to the new alarm. (New alarms are defined as those that are not currently shown within the display object.)
ColorPriorityRange1
Integer
Sets the boundary of the priority range in which alarms are to be shown. The value of this property must be greater than one and less than the value for ColorPriorityRange2.
ColorPriorityRange2
Integer
Sets the boundary of the priority range in which alarms are to be shown. The value of this property must be greater than the value for ColorPriorityRange1 and less than the value for ColorPriorityRange3
ColorPriorityRange3
Integer
Sets the boundary of the priority range in which alarms are to be shown. The value of this property must be greater than the value of ColorPriorityRange2 and less than 999.
ColumnResize
Discrete
Returns or sets a value that determines whether the columns can be resized at run time.
CustomMessage
Message
The default message to show when there are no alarms.
DefaultAckComment
Message
Used as a comment when the alarm is acknowledged and when the “UseDefaultAckComment” is TRUE. Otherwise, the user is prompted to enter a comment.
DisplayedTime
Message
Shows the alarm message time. The values can only be “OAT” or “LCT” or “LCT But OAT on ACK.”
DisplayedTimeZone
Message
Gets or sets the current time zone string. The values can only be “GMT” or “Origin Time” or “Local Time.”
EventColor
Integer
Sets color of events.
ExtendedSelection
Discrete
Allows you to select multiple alarms by holding down the Ctrl or Shift key in conjunction with the mouse button. The default is to toggle selection of alarms by simply clicking on them (available only if the Row Selection check box is selected).
FlashUnAckAlarms
Discrete
Enables or disables the flashing of unacknowledged alarms. It takes a discrete input value of 1 or 0. If this property is set to 1, unacknowledged alarms flash once per second. If this property is set to 0, unacknowledged alarms do not flash. This property corresponds to the Flash Unack Alarms check box on the Alarm Viewer control General tab.
FlashUnackAlmColorRange1
Integer
Sets the flashing color for unacknowledged alarms belonging to Alarm Priority Range 1.
FlashUnackAlmColorRange2
Integer
Sets the flashing color for unacknowledged alarms belonging to Alarm Priority Range 2.
FlashUnackAlmColorRange3
Integer
Sets the flashing color for unacknowledged alarms belonging to Alarm Priority Range 3.
FlashUnackAlmColorRange4
Integer
Sets the flashing color for unacknowledged alarms belonging to Alarm Priority Range 4.
Font
None
Sets the font for the records and the header in the control.
FreezeMenu
Discrete
Enables/disables the Freeze menu item.
FromPriority
Integer
Sets the low priority value of the default query.
GridColor
Integer
Sets the color of the background grid.
NewAlarmEventMode
Integer
Controls the triggering of the NewAlarm event.
0 = The NewAlarm event can not be triggered. (Default).
1 = The NewAlarm event is active.
2 = The NewAlarm event is active and continually triggers when at least one new unacknowledged alarm arrives.
QueryFavoritesFile
Message
Returns or sets the query favorites file name.
QueryFavoritesMenu
Discrete
Enables/disables the Query Favorites menu item.
QueryName
String
Returns the current query name.
QueryStartup
Discrete
Automatically begins updating the grid using default query properties, if set. Otherwise, you must run the ApplyDefaultQuery or ApplyQuery method in a script to update the grid.
QueryType
Message
Sets the display type as either Summary or Historical.
RequeryMenu
Discrete
Enables/disables Requery shortcut menu item.
RetainSuppression
Discrete
Retains alarm suppression between alarm queries when the alarm query is changed.
RowSelection
Discrete
Allows user to select alarms during run time.
SecondarySortColumn
Message
Returns or sets the current secondary sort column.
SelectedCount
Integer
Returns the total number of selected alarms.
ShowContextMenu
Discrete
Enables the activation of the shortcut menu.
ShowGrid
Discrete
Returns or sets a value that determines whether the grid lines are shown in the control.
ShowHeading
Discrete
Shows the title bar of the control.
ShowMessage
Discrete
Returns or sets a value that determines whether error messages are shown for the control.
ShowStatusBar
Discrete
Gets or sets a value that determines whether the status bar is shown.
SilentMode
Discrete
Gets or sets a value that determines whether the control is in silent mode.
SortColumn
Message
Gets or sets the current sort column.
SortMenu
Discrete
Enables/disables the Sort menu item.
SortOrder
Discrete
Gets or sets the sort direction. Possible values are “Ascending” and “Descending,” represented as 0 and 1 respectively.
StatsMenu
Discrete
Enables/disables the Stats menu item.
SuppressAllMenu
Discrete
Enables/disables the Suppress All menu item.
SuppressedAlarms
Integer
Gets the total number of suppressed alarms.
SuppressionMenu
Discrete
Enables/disables the Suppression menu item.
SuppressOthersMenu
Discrete
Enables/disables the Suppress Others menu item.
SuppressSelectedGroupsMenu
Discrete
Enables/disables the Suppress Selected Groups menu item.
SuppressSelectedMenu
Discrete
Enables/disables the Suppress Selected menu item.
SuppressSelectedPrioritiesMenu
Discrete
Enables/disables the Suppress Selected Priorities menu item.
SuppressSelectedTagsMenu
Discrete
Enables/disables Suppress Selected Tags menu item.
SuppressVisibleMenu
Discrete
Enables/disables the Suppress Visible menu item.
TimeFormat
Message
Sets the format of the alarm time stamps.
TitleBackColor
Integer
Sets title bar background color.
TitleForeColor
Integer
Sets title bar foreground color.
ToPriority
Integer
Sets the maximum priority for the alarm query.
TotalAlarms
Integer
Gets the number of alarms.
UnackAlarms
Integer
Gets the total number of unacknowledged alarms.
UnAckAlmColorRange1
Integer
Sets the color to be used to show unacknowledged alarms with priorities in the range of 1 to ColorPriorityRange1.
UnAckAlmColorRange2
Integer
Sets the color to be used to show unacknowledged alarms with priorities in the range of ColorPriorityRange1 to ColorPriorityRange2.
UnAckAlmColorRange3
Integer
Sets the color to be used to show unacknowledged alarms with priorities in the range of ColorPriorityRange2 to ColorPriorityRange3.
UnAckAlmColorRange4
Integer
Sets the color to be used to show unacknowledged alarms with priorities in the range of ColorPriorityRange3 to 999.
UnsuppressAllMenu
Discrete
Enables/disables Unsuppress All menu items.
UseDefaultAckComment
Discrete
If set to True, the default acknowledgement comment is used when the alarm is acknowledged. Otherwise, the operator is prompted to enter a comment.
WindowColor
Integer
Sets the grid background color.
Control ActiveX Control ActiveX Control ActiveX Control ActiveX Control ActiveX Control ActiveX Control ActiveX Control ActiveX Control ActiveX